i.LON SmartServer 2.0 Programmer’s Reference
18-2
<xSelect>//*[@xsi:type="FileSystem"][UCPTname="/eventlog.txt"][UCPTfileFormat="text"]</xSelect>
</iLonItem>
</Read>
Request (return the data in a Data Logger)
<Read xmlns="http://wsdl.echelon.com/web_services_ns/ilon100/v4.0/message/">
<iLonItem>
<xSelect>//*[@xsi:type="FileSystem"][UCPTname="/root/data/Net/LON/iLON App/Data
Logger[1].csv"][UCPTfileFormat="text"]</xSelect>
</iLonItem>
</Read>
Response
<Read xmlns="http://wsdl.echelon.com/web_services_ns/ilon100/v4.0/message/">
<iLonItem>
<Item xsi:type="FileSystem_Data">
<UCPTname>/root/data/Net/LON/iLON App/Data Logger[1].csv</UCPTname>
<UCPTlastUpdate>2008-02-27T21:41:56Z</UCPTlastUpdate>
<UCPTdescription />
<UCPTfileFormat LonFormat="UCPTfileFormat">text</UCPTfileFormat>
<UCPTfileSize>98052</UCPTfileSize>
<Value>
"UCPTlogTime","UCPTpointName","UCPTaliasName","Reserved","UCPTpointStatus","UCPTvalueDef","UC
PTvalue","UCPTunit","UCPTpriority"
2008-02-27T13:41:57.440-08:00,"Net/LON/iLON App/Digital Input
2/nvoClsValue_2","NVL_nvoClsValue_2","","AL_NO_CONDITION","OFF","0.0 0","","255"
2008-02-27T13:45:00.000-08:00,"Net/LON/iLON App/Digital Input
2/nvoClsValue_2","NVL_nvoClsValue_2","","AL_NO_CONDITION","OFF","0.0 0","","255"
2008-02-27T14:00:00.040-08:00,"Net/LON/iLON App/Digital Input
2/nvoClsValue_2","NVL_nvoClsValue_2","","AL_NO_CONDITION","OFF","0.0 0","","255"
</Value>
</iLonItem>
<Read>
The following C# sample code demonstrates how to read a file in hex mode:
ilonWebRef.Item_Coll itemColl = new ilonWebRef.Item_Coll();
itemColl.xSelect =
"//*[@xsi:type=\"FileSystem\"][UCPTname=\"/root/data/myfile.txt\"][UCPTfileFormat=\"hex\"]";
ilonWebRef.Item_DataColl readResp = ilon.Read(itemColl);
if (readResp.UCPTfaultCount > 0)
MessageBox.Show(readResp.fault.faultstring);
else
String str = (readResp.Item[0] as ilonWebRef.FileSystem_Data).Value;
Note: You can read and write file system data that includes new line characters. For example, using
the Read function on the following file system data:
<Read xmlns="http://wsdl.echelon.com/web_services_ns/ilon100/v4.0/message/">
<iLonItem>
<Item xsi:type="FileSystem_Data">
<UCPTname>/data/writetest.txt</UCPTname>
<UCPTfileFormat>text</UCPTfileFormat>
<Value>
Hello
World
!
</Value>
</Item>
</iLonItem>
<Read>