6-2
<Item xsi:type="UFPTalarmGenerator_Cfg" >
<UCPTname>Net/LON/iLON App/Alarm Generator[0]</UCPTname>
<UCPTannotation>8000010128000000[4].UFPTalarmGenerator</UCPTannotation>
<UCPThidden>0</UCPThidden>
<UCPTlastUpdate>2008-02-28T15:29:23.220-08:00</UCPTlastUpdate>
<UCPTuri>#8000010128000000[4].UFPTalarmGenerator_Cfg.htm</UCPTuri>
<DataPoint dpType="nviEnable" discrim="dir_in" >
<UCPTname>Net/LON/iLON App/Alarm Generator[0]/nviAgEnable[0]</UCPTname>
</DataPoint>
<DataPoint dpType="nvoAlarmFlag" discrim="dir_out" >
<UCPTname>Net/LON/iLON App/Alarm Generator[0]/nvoAgAlarmFlag[0]</UCPTname>
</DataPoint>
<DataPoint dpType="nviLatchEnable" discrim="dir_in" >
<UCPTname>Net/LON/iLON App/Alarm Generator[0]/nviAgLatchEnbl[0]</UCPTname>
</DataPoint>
<DataPoint dpType="Input" discrim="dir_in" >
<UCPTname>Net/LON/iLON App/Digital Output 1/nviClaValue_1</UCPTname>
</DataPoint>
<DataPoint dpType="Compare" discrim="dir_in" >
<UCPTname>Net/LON/iLON App/Alarm Generator[0]/CompareDP</UCPTname>
</DataPoint>
<UCPTalrmIhbD>0.000000</UCPTalrmIhbD>
<UCPTalarmPriority LonFormat="UCPTalarmPriority">PR_LEVEL_1</UCPTalarmPriority>
<UCPTpollOnResetDelay>0.0</UCPTpollOnResetDelay>
<UCPTpollRate>0.0</UCPTpollRate>
<UCPTalarm2Description></UCPTalarm2Description>
<UCPTcompFunction LonFormat="UCPTcompFunction">FN_EQ</UCPTcompFunction>
<UCPTalarmSetTimeD>0.000000</UCPTalarmSetTimeD>
<UCPTalarmClrTimeD>0.000000</UCPTalarmClrTimeD>
<UCPTlowLimit1Offset LonFormat="UNVT_double_float"></UCPTlowLimit1Offset>
<UCPTlowLimit2Offset LonFormat="UNVT_double_float"></UCPTlowLimit2Offset>
<UCPThighLimit1Offset LonFormat="UNVT_double_float"></UCPThighLimit1Offset>
<UCPThighLimit2Offset LonFormat="UNVT_double_float"></UCPThighLimit2Offset>
<SCPThystHigh1 LonFormat="UNVT_double_float"></SCPThystHigh1>
<SCPThystHigh2 LonFormat="UNVT_double_float"></SCPThystHigh2>
<SCPThystLow1 LonFormat="UNVT_double_float"></SCPThystLow1>
<SCPThystLow2 LonFormat="UNVT_double_float"></SCPThystLow2>
</Item>
6.2
Creating and Modifying the Alarm Generator XML File
You can create and modify the #8000010128000000[4].UFPTalarmGenerator.xml file with the Set
SOAP function. The following section,
Alarm Generator SOAP Interface, describes how to use the Set
function, and the other SOAP functions provided for the Alarm Generator application.
Alternatively, you can create and modify the #8000010128000000[4].UFPTalarmGenerator.xml file
manually using an XML editor, and download the file to the SmartServer via FTP. Echelon does not
recommend this, as the SmartServer will require a reboot to read the configuration of the downloaded
file. Additionally, the SmartServer performs error checking on all SOAP messages it receives before
writing to the XML file. It will not perform error checking on any XML files you download via FTP,
and thus the application may not boot properly.
However, if you plan to create and manage the XML file manually, you should review the rest of this
chapter first, as it describes the elements and properties in the XML file that define each Alarm
Generator’s configuration.
6.3
Alarm Generator SOAP Interface
The SOAP interface for the Alarm Generator application includes the following functions:
Function Description
List Generate a list of the Alarm Generators that you have added to the
SmartServer.